0, 46019
Business Type:
Manufacturer/Factory
Business Range:
Power Cable,Rubber Cable,Electric Wire,Control Cab,
Management System Certification:
Terms of Payment:
LC, T/T, Western Union
OEM/ODM Availability:
Yes
OEM/ODM Service
Sample Available
MEI Awards
Trial Member 4 years
Audited Supplier
Supplier Homepage Electronic Electronic circuit cooling components heat sink N2xsy/Na2xsy Electric Single Core XLPE Insulated Copper Wire Shield 11kv Aluminum Power Armour Cable

N2xsy/Na2xsy Electric Single Core XLPE Insulated Copper Wire Shield 11kv Aluminum Power Armour Cable

Purchase Qty. / Reference FOB Price
Production Capacity:
Payment Terms: LC, T/T, Western Union

Basic Info

Model NO.
N2XSY/NA2XSY
Material Shape
Round Wire
Range of Application
Flame Retardant
Certification
ISO9001, CE, CCC
Brand
Ren Da
Rated Voltage
11kv
Cross Section
25mm2-630mm2
Cores
Single or Three
Certificate
TUV Psb UL
Conductor
Alulminum or Copper
Product Name
N2xsy/Na2xsy Cable
Sheild
Copper Wire Plus Copper Tape
Sheathed Material
PVC
Sheathed Color
Red or Black
Package
Steel Wooden Drum or Wooden Drum
Trademark
RNE DA
Transport Package
Standard Export Drum
Specification
IEC60502
Origin
Hebei, China
HS Code
85444921

Single Core XLPE Insulated Copper Wire Shield 11kv Aluminum Power Cable



1. Object
This document defines the design and manufacturing characteristics of the cables type
RHZ1-OL 12/20 kV Al+H16 manufactured by HuaTong Cables.
2. Design
This type of cables is designed, manufactured and tested according to UNE-HD 620-10E and
IEC 60502-2.

3. Applications

Cables for fixed installations. Suitable for transport and distribution of electric power in
medium voltage networks. Halogen-free. These cables are suitable for indoor, outdoor and
buried installations.

 4. Characteristics
Nominal voltage: 12/20 (24) kV
Minimum service temperature: -15 °C
Maximum conductor temperature: 90 °C
Maximum short-circuit temperature: 250 °C (maximum 5 s)
Minimum bending radius: 15 x cable Ø
Halogen-free: according to EN 50267 / IEC 60754
HCl content < 0,5 %
pH > 4,3
conductivity < 10 μS/mm

5. General make-up of the cable
5.1 Conductor
Electrolytic annealed aluminum conductor, class 2 according to EN 60228 / IEC 60228.
Optionally, hygroscopic tapes can be applied to achieve longitudinal water-tightness
on the conductor (cable type -2OL)
5.2 Inner semi-conducting screen
Cross-linked semiconductor screen applied over the conductor in a triple-extrusion process.
5.3 Insulation
Cross-linked polyethylene insulation, type DIX-3 according to HD 620-1 and type XLPE
according to IEC 60502-2; natural color. Cross-linked in catenary line with nitrogen
atmosphere.
5.4 Outer semi-conducting screen
Cross-linked semiconductor screen applied over insulation in a triple-extrusion process.
Strippable.
Optionally, under customer requests, it can be supplied non-strippable (bonded to insulation).
5.5 Metalic screen
The metallic screen made with Cu wires and Cu binder tape, applied over the outer semiconducting
layer. 
5.6 Water blocking
The hygroscopic tape is applied over the metallic screen.
5.7 Outer sheath
Polyolefine outer sheath, type DMZ1 according to HD 620-1 and type ST7 according to IEC
60502-2; red color.
6 Datasheet:

Cross-sectionScreenConductorInsulationOuter Weight
mm2mm2mmmmmmKG/KM
1x5016820.227.9770
1x70 1610.122.330.4905
1x951611.323.531.51000
1x1201612.724.933.61140
1x1501614.226.435.11260
1x185161628.236.91405
1x240161830.239.41635
1x300162133.242.41865
1x4001623.436.445.62225
1x500162740.449.22585
1x6301631.544.553.73130
1x80016344757.23775
1x1000163951.760.54450







 

Send Inquiry to this supplier

Send Inquiry to this supplier

Service Tel: (+86)0571-87774297